Switching a Furnace from Diesel or Oil to PNG: Costs and Savings
Many Indian furnaces and ovens were built to burn diesel, LDO or furnace oil. Today most owners we speak to want to move away from them. Pollution rules in NCR, the smoke and soot, oil handling, and the hassle of pumping and heating heavy oil all push the same way.
PNG (piped natural gas) is the usual replacement where a pipeline is available. This guide explains what a conversion involves, what saving to expect, and how to protect yourself from the gas supply problems seen in 2026. Advance Heating Systems no longer supplies diesel-fired equipment; we build and retrofit gas, electric and dual-fuel heating systems.
Key takeaways
BEE's forging study estimates an oil-to-gas switch saves 5–10% of fuel energy, on top of savings from better control.
A conversion usually means a new gas burner, gas train, flame safety and controls, and sometimes changes to the combustion chamber.
Air-fuel ratio matters: BEE recommends 1.12–1.15 for gas versus 1.15–1.20 for liquid fuel.
Gas is cleaner and easier to control, but supply and price risk are real. In 2026 some industrial users were capped at 40% of contracted gas.
Consider a dual-fuel design (gas + electric, or PNG + LPG) to keep production running.
Check the current CAQM rules if you are in Delhi NCR.
Why owners are moving off diesel and oil
Rules
In Delhi NCR, CAQM's 2022 order set out approved fuels for industry, including PNG, and banned coal from 1 January 2023. In 2026 the particulate limit for targeted industries was tightened to 50 mg/Nm³ from 1 October 2026, with exemptions possible for units using only clean fuels and having no particulate source (Down To Earth). Read our CAQM guide for details.
Operations
Oil firing brings practical headaches:
oil storage and day tanks;
heating and pumping units for heavy oil;
nozzle and filter cleaning;
soot on the product and in the furnace.
Process quality
Gas gives finer temperature control. BEE found that oil and gas furnaces in forging clusters often overheat metal by 10–30°C. Better burner control reduces that waste and scale.
What calorific values tell you
The CEA's fuel data gives these gross calorific values:
Fuel | Gross calorific value |
HSD (diesel) | 10,600–11,300 kcal/kg |
LDO | 10,530 kcal/kg |
LSHS | 10,350–10,532 kcal/kg |
LSFO | 10,300 kcal/kg |
Natural gas | 8,371–10,000 kcal/SCM, depending on source |
To estimate gas use after conversion, start from your current oil consumption:
SCM of gas per hour ≈ (kg of oil per hour × oil kcal/kg) ÷ gas kcal/SCM × (1 − expected saving)
Example (illustrative only): a furnace burning 20 kg/hour of LDO uses about 2,10,600 kcal/hour. At 9,000 kcal/SCM and a 7% saving, that is about 22 SCM/hour of PNG. Ask your gas supplier for their calorific value and your all-in price per SCM.
What a conversion involves
1. Survey
We check the furnace size, working temperature, existing burner position, combustion chamber, flue, refractory condition and controls. We also note your current oil consumption and production.
2. Burner selection
The gas burner is sized for the heat load. Options include:
self-proportional or mono-block gas burners with auto ignition;
high-velocity burners for better circulation in heat-treatment furnaces;
multiple smaller burners for zone control.
See our industrial gas burners and CNG burners.
3. Gas train and safety
A proper gas train is not optional. A BIS draft guideline for fuel-fired reheating furnaces lists these safety items (BIS draft, IS 17082 revision):
safety shut-off valves, filters and governors;
high and low gas pressure switches;
UV flame monitoring, with flame failure cutting off fuel;
over-temperature cut-off with audio-visual alarm.
Our burner systems include flame-failure gas cut-off with alarm as standard.
4. Combustion chamber and flue
Gas flames have a different shape and heat release from oil flames. The burner block, firing chamber or baffles may need changes. A flue damper helps hold the right furnace pressure.
5. Commissioning and tuning
The burner is tuned for the right air-fuel ratio. BEE recommends 1.12–1.15 for gas. Too much air wastes heat up the flue; too little wastes fuel and causes soot.
How much will you save?
BEE's Forging Sector Energy Mapping Report estimates:
5–10% saving from switching oil to gas;
10–35% overall saving potential across furnaces and auxiliaries, from better combustion, insulation and heat recovery.
So the fuel switch alone is a modest saving. The bigger gains come when you combine it with:
correct air-fuel ratio;
flue exit temperature of about 250–300°C (BEE target);
better insulation, such as ceramic fibre relining;
proper temperature control.
Your rupee saving also depends on the price of oil versus gas at the time, which changes often.
The 2026 lesson: plan for gas supply risk
Gas is not risk-free. In 2026, after the West Asia disruption:
Adani Total Gas asked industrial and commercial customers to limit use to 40% of contracted volume, and charged gas above that at an excess rate that was cut from ₹119.90 to ₹82.95/SCM in March 2026.
In Morbi, industrial PNG rose about 80% to about ₹75/m³.
Earlier, CSE found NCR industries receiving only 70–80% of contracted PNG and buying the rest at spot rates about four times higher.
How to protect yourself
Dual-fuel burners: some burners can switch between natural gas and LPG.
Gas + electric: our dual-fuel ovens switch between gas and electric heating at a selector switch on the panel.
Better insulation: every kcal saved is a kcal you do not have to buy at spot price.
When electric makes more sense than PNG
For ovens running below about 400°C, an electric oven may be close to PNG on running cost in 2026, with no combustion emissions and no gas supply risk. Our running cost comparison shows the maths. For high-temperature reheating and heat treatment, gas usually remains the practical choice.
Frequently asked questions
Can I convert my oil-fired furnace to PNG? Usually yes. It needs a new gas burner, gas train, flame safety and tuning, and sometimes changes to the combustion chamber. A site survey confirms the scope.
How much fuel will I save by switching from oil to gas? BEE estimates 5–10% from the switch itself. More comes from better air-fuel control, insulation and heat recovery.
What air-fuel ratio should a gas furnace run at? BEE recommends 1.12–1.15 for gas.
Is PNG allowed in Delhi NCR? Yes. PNG is on CAQM's approved fuel list for NCR industry.
What if gas supply is cut? Plan a backup: a dual-fuel burner for PNG and LPG, or a gas + electric oven design.
Plan your conversion with AHS
Send us your furnace type, size, working temperature and current oil consumption. We will advise on a PNG, dual-fuel or electric option and quote for the retrofit. Steel and forging units can also see our steel, forging and casting industries page.